Mitsubishi Electronics FX3U-CF-ADP Video Gaming Accessories User Manual


 
10 Troubleshooting
10.1 Troubleshooting procedure
104
FX3U-CF-ADP User's Manual
503 ID table read error
The file management information was not able to be read from the
CompactFlash
TM
card.
When reading or deleting a file, confirm that the target file exists.
504 ID table corruption error The file management information is corrupt.
505 ID table not found
The file management information does not exist in the
CompactFlash
TM
card.
600 Parity, Framing, Overrun error
Check the connection to the main unit.601 Communication character error
602 Communication sum error
603 Outside channel number range
Check the version of the main unit.
Something may be wrong with the hardware.
Contact your local Mitsubishi Electric distributor.
604 Undefined command error
605 Time check error
606 Address error inside adapter
607 Consecutive execution serial number error
608
Consecutive execution serial number error (serial
number)
609 Outside data type range
The data type specified during file creation is different from the data
type to be written.
610 Outside transfer point number range
Check the version of the main unit.
Something may be wrong with the hardware.
Contact your local Mitsubishi Electric distributor.
611 Total transfer point number error
612
Transfer point number error, minimum value error or
maximum value error in each type
613 Outside single type or mixed type command range
614 Mixed type data in single type command
615
Mismatch between total number of points and sum of
number of points of each type
616 Deletion method error
617 Outside FAT format range
619 Outside error code clear command range
620 Divided character string receiving error
700 Command execution error
701 Command sequence error
702 Data name not set in head record
The data name can be written only in the head line.
Check whether data does not exist in the writing target file.
703 ACCESS switch OFF error Check whether the ACCESS switch is set to ON.
704 Access error in unmounted status
Check whether the SLOT LED or M8405/M8425 (CF card mounting
status) is ON.
If the SLOT LED or M8405/M8425 is OFF, pull out the
CompactFlash
TM
card once and insert it again, or execute
CompactFlash
TM
card mounting processing. Confirm that the SLOT
LED or M8405/M8425 turns ON, and then execute the instruction
again.
801 File ID specification error
The specified file ID does not exist.
Check whether the specified file ID has been used.
802 CF file ID number error
The specified file ID is outside the setting range.
Specify the file ID within the range from 0 to 63.
803 CF file ID duplication error
The specified file ID already exists.
If the specified file already exists, the same file cannot be created or
confirmed because parameters set at file creation are changed. When
the file has already been created, confirm the parameters. When the
file has not been created yet, delete the existing file or specify another
file ID.
804
Existing file line position larger than specified
maximum line position
The maximum line position of the target file to be associated is larger
than the maximum line position of the file specified in the file creation
instruction.
Review the maximum line position in the file creation instruction.
Error
code
Error definition Error corrective action