4-2SectionProgramming Console Operations
53
RUN MONITOR PROGRAM
No OK OK
The timer or counter SV can be changed either by inputting a new value or
by incrementing or decrementing the current SV.
This operation can be used to input a new SV constant, as well as to change an
SV from a constant to a word address designation and vice versa. The following
examples show how to input a new SV constant and how to change the SV from
a constant to an address.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM
B
1
SRCH
00201SRCH
TIM 001
3. Press the Down Arrow Key and then the CHG Key.
CHG
00201DATA?
T001 #0134 #????
4. At this point a new SV constant can be input or the SV constant can be
changed to a word address designation
a) To input a new SV constant, input the constant and press the WRITE
Key.
B
1
C
2
E
4
WRITE
00201 TIM DATA
#0124
b) To change to a word address designation, input the word address and
press the WRITE Key.
SHIFT
CH
*DM
AR
HR
B
1
A
0
WRITE
00201 TIM DATA
HR 10
This operation can be used to increment and decrement an SV constant. It is
possible only when the SV has been entered as a constant.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
2. Display the desired timer or counter.
TIM
SRCH
00201SRCH
TIM 000
3. Press the Down Arrow, CHG, and then the EXT Key.
CHG
EXT
00201DATA ? U/D
T000 #0123 #0123
The constant on the left is the old SV and the constant on the right will be-
come the new SV constant in step 5.
4. Press the Up and Down Arrow Keys to decrement and increment the
constant on the right. (In this case the SV is incremented once.)
00201DATA ? U/D
T000 #0123 #0124
5. Press the CLR Key twice to change the timers SV to the new value.
CLR CLR
00201 TIM DATA
#0124
4-2-21 Hexadecimal, BCD Data Modification
This operation is used to change the BCD or hexadecimal value of a word
being monitored using the procedure described in 4-2-13 Bit, Digit, Word
Monitor. It is possible in MONITOR or PROGRAM mode only.
Inputting a New SV
Constant
Incrementing and