Omron srm1(-v2) Video Game Controller User Manual


 
4-2SectionProgramming Console Operations
52
1, 2, 3... 1. Monitor the word that is to be used for decimal monitor without sign. During
multiple address monitoring and 3-word monitoring, the leftmost word will
be converted.
Multiple address monitoring
c200 cL0020000
FFF0 0000^ OFF
2. Press the SHIFT+TR+NOT Keys to display the leftmost word as unsigned
decimal.
SHIFT TR
NOT
c200
65520
At this point, the contents of the displayed word can be changed with an un-
signed-decimal input. Refer to 4-2-24 Unsigned Decimal Data Modification.
3. Press the CLR Key or the SHIFT+TR Keys to end the unsigned decimal dis-
play and return to normal monitoring.
CLR
c200 cL0020000
FFF0 0000^ OFF
4-2-19 Three-Word Data Modification
This operation is used to change the contents of one or more of the 3 con-
secutive words displayed in the 3-Word Monitor operation. It is possible in
MONITOR or PROGRAM mode only.
RUN MONITOR PROGRAM
No OK OK
1, 2, 3... 1. Monitor the status of the desired words according to the procedure de-
scribed 4-2-16 3-Word Monitor.
(3-word monitor)
D0002D0001D0000
0123 4567 89AB
2. Press the CHG Key to begin 3-word data modification. The cursor will ap-
pear next to the contents of the leftmost word.
CHG
D0002 3CH CHG?
00123 4567 89AB
3. Input the new value for the leftmost word on the display and press the CHG
Key if more changes will be made.
(Input the new value and press the WRITE Key to write the changes in
memory if no more changes will be made.)
B
1
CHG
D0002 3CH CHG?
0001 4567 89AB
4. Input the new value for the middle word on the display and press the CHG
Key if the rightmost word will be changed. Input the new value and press the
WRITE Key to write the changes in memory if the rightmost word will not be
changed. (In this case, it will not.)
C
2
D
3
E
4
WRITE
D0002D0001D0000
0001 0234 89AB
Note If the CLR Key is pressed before the WRITE Key, the operation will be cancelled
and the 3-word monitor display will return without any changes in data memory.
4-2-20 Changing Timer, Counter SV
There are two operations that can be used to change the SV of a timer or
counter. They are possible in MONITOR or PROGRAM mode only. In MONI-