ALARM HANDLING EXCEL 50/100/500/600/800
EN2B-0092GE51 R0512 48
Alarm
no.
alarm text
English)
cond.
code #
cause/reason
48 Part applic. miss
46
47
48
49
52
1) No RACL program.
2) No parameter file.
3) No Z register file.
4) No T register file.
5) No datapoint description.
49 RACL environ fault
26 1) Submodule does not exist.
27 2) Parameter file missing.
28 3) No M0 module.
31 4) Invalid SKIP destination.
34 5) Info points STARTUP, SHUTDOWN, or EXECUTING_STOPPED are missing or
6) During RACL start datapoint contains errors.
1
7) freely programmable application loaded into Excel 50 controller (system alarm
parameters set to 0,0,0).
50 INIT div. by zero 14 Reason of new start: Division by zero.
51 INIT under OpCode 15 Reason of new start: the system software contains an undefined Operation Code.
52 Power failure 16 Reason of new start: power failure, data in RAM ok.
53 Link Config Bad - Xlink alarm.
54 I/O board missing 19
The required configuration contains at least one module which is not included in the
hardware configuration.
55 Unused I/O board 18
The hardware configuration contains at least one module that is not needed (can be taken
out).
56 HW Config. failure 20
1) Hardware Configuration file (.kfx file) not complete loaded.
2) Different modules are plugged under the same address (set using the rotary HEX
switch) in the required configuration and in the hardware configuration.
3) An application containing NV-mapping is rejected by the target controller because the
hardware does not have the 3120E5 Neuron® chip.
57 Wrong version no. 21 The version number of the application files and the configuration file are not the same.
58 Totalizer overflow 5 Overflow operation hours counter, point value of counters and interval impulse counter.
59 Maintenance alarm 7
Course of a service interval for digital points or course or the message/calling interval for
counters. Call intervals for counters.
60 Undef. RACL input 62 Undefined RACL errors.
61 Too many Globals 63
The loaded application contains too many remote points. An application with more than 46
NVs has been rejected for download into an Excel 50 freely programmable controller
located on a L
ONWORKS network.
62 C-Bus error 64
Communication defect/disturbance between Excel 500 and C-Bus submodule. Logical
modem device in controller has gotten a C-Bus # already in use for a C-Bus controller.
63
No Globals
memory
9 No remote storage; the remote controller has no storage left for requested remote points.
64 Global pnt missing 10 The user address of the remote point was not found in the remote controller.
65 Glob Pnt Occupied 11 A remote output to a remote controller is already assigned to another controller.
66 CPU stopped 12 The remote controller is in stopped condition.
67 CPU not available 13 The remote controller is switched off or does not respond to C-Bus communication.
68 Init. actuators 65 Floating outputs (3-position outputs) are synchronized.
69 WARM START 66 Reason of new start: watchdog.
70 COLD START 67 Reason of new start: power failure, data in RAM destroyed.
71 Point in manual 68 When falling back to password level 3 there are still points in manual override.
72 Report too large 69 Not enough space in the report file for initialization.
73 XI 581 required 70
After a download, an entry is demanded in the initializing phase of the ASPECD
application. This can happen only with XI581 emulation.
74 New appli. loaded 74 Download of a new application part or entire application.