Honeywell R0512 Video Game Controller User Manual


 
ATTRIBUTES EXCEL 50/100/500/600/800
EN2B-0092GE51 R0512 14
Active State (prior to V2.04.x)
The attribute "Active State" defines when a digital input/output is active.
NOTE: The "Active State" attribute does not reflect the current condition of a
digital datapoint.
NOTE: This is not applicable to digital inputs in applications designed for con-
trollers using V2.04.xx firmware or higher. In such applications, this
attribute is fixed at 1, and the new attribute "Normally Open/Normally
Closed" (NO/NC) is active (see section "Normally Open/Normally Closed
(V2.04.xx or higher)" on page 28 for more details).
The following values are possible:
0 = digital input/output is active when a "logical 0 signal" is present
1 = digital input/output is active when a "logical 1 signal" is present
Table 3 indicates the active state for various conditions of the XF523 and XFL523
modules.
Table 3. Active state for the digital input of XF523 and XFL523 modules
digital input
contact status open closed
CARE definition
(NC/NO system diagram)
NC NO NC NO
definition - in XL-Online DP-
Editor attribute "Active State"
(change Active/Passive State
text)
1 0 1 0 1 0 1 0
CARE interpretation
(control table)
1 1 0 0 0 0 1 1
display at operator interface
(status text)
OFF/
trouble:
alarm
ON/
operating
RTN*
OFF/
trouble:
alarm
ON/
operating
RTN*
ON/
operating
RTN*
OFF/
trouble:
alarm
ON/
operating
RTN*
OFF/
trouble:
alarm
* RTN = Return To Normal
NOTE: XFL523 Module is applicable only for V2.0.xx software.
Active State (Excel 800)
The attribute "Active State" defines when a digital input/output is active. 1 means,
that a digital input/output is active when a "logical 1 signal" is present
NOTE: "Active State" = 0 is not allowed/possible.
NOTE: The "Active State" attribute does not reflect the current condition of a
digital datapoint.
Table 4. Active State for the digital input of XF823 and XFL823 modules
digital input
contact status
open closed
CARE definition
(NC/NO system diagram)
NC NO NC NO
definition - in XL-Online DP-
Editor attribute "Active State"
(change Active/Passive State
text)
1 1 1 1