EXCEL 50/100/500/600/800 ALARM HANDLING
EN2B-0092GE51 R0512
47
Alarm
no.
alarm text
English)
cond.
code #
cause/reason
14 Return to normal 79 Alarm condition control for DI, PD points.
15 Hware clock failed 61 Error while initializing the system clock.
16 Battery low 17 Battery voltage too low or battery not existent.
17 Battery status OK 87
Battery voltage back to normal again (alarm occurs only after alarm message "Battery
low").
18 Wrong Module ID 71
An invalid module ID is read (error on internal I/O or defect module or the module has an
as-yet unspecified module ID).
19
Too Many DO
Module
60 Too many modules of the same type (XF521, XF522, ...).
20 Contr. w/o Flash 81 Error occurred when burning the Flash EPROM.
21 FLASH Mem Full 82 Not enough Flash memory space to save application.
22 Link Point Alarm - Xlink alarm.
23 Link Comm Down - Xlink alarm.
24 No characteristic 57 The application part "Characteristics" is defect.
25
RCL Submod
missing
- RACL sub-module missing.
26 Download SSI Now - Xlink alarm.
27
Download CPU
Now
- Xlink alarm.
28 RACL inconsistent 29
Incompatible version numbers of RACL program and RACL parameter files and/or
datapoint description.
29
Nested
submodules!
30 RACL program contains errors (MCAL from submodule).
30
alarm message
158
- Alarm not used.
31
RACL undef.
OpCode
32 RACL program contains errors (undefined Operation code).
32
RACL program
fault
33 RACL program contains errors (Checksum changed).
33 Unknown datapoint 34
1) During RACL run, datapoint contains errors or point is locked.
2) An unrecognized (missing) characteristic in the datapoint editor has been used.
Check if the default file set of the controller is different from the set used in CARE.
34 SSI Points Active Xlink alarm.
35 Invalid operation 36
Non-valid arithmetical operation during RACL performance (e.g. division by zero or RACL
statements LN with input value 1.0 ).
36 RACL overflow 37 Arithmetic overflow at RACL performance "+infinite".
37
RACL neg.
overflow
38 Arithmetic underflow at RACL performance "-infinite".
38
RACL inval.
OpCode
39 RACL program contains errors (invalid Operation Code).
39 Z-Reg. index error 40 Access to non-existing Z register (e.g.: RACL statements ISTO and IRCL).
40 Invalid Y-Register 41 Too many statements (exits) in one column.
41 Invalid P-Register 42 Attempt to use non-existent P register.
42 Invalid T-Register 43 Attempt to use non-existent T register.
43 Invalid Z-Register 44 Attempt to use non-existent Z register.
44 SSI Interface Up - Xlink alarm.
45 No parameter file - RACL parameter file missing.
46 No Z file - RACL Z register file missing.
47 No T file - RACL time register file missing.