A SERVICE OF

logo

46 InfraStruXure InRow RC Service
Condensate Pump
Tools
T20 Torx screwdriver, #2 Standard screwdriver
1. Remove power to the unit by disconnecting both power cords (feed A and feed B).
2. Lockout/tagout the unit being serviced.
3. Remove the rear door and the bottom air filter.
4. Use a standard screwdriver
to remove the plastic
pushclips securing the cover.
Remove the plastic cover
from the electronic
components.
5. Disconnect the power
connection to the condensate
pump (labeled PMP).
6. Disconnect the hoses
connecting the condensate
pump to the drain pan and to
the drain outlet, not at the
pump but out along the
hoses.
Warning
This device may be connected to more than one input power source. Verify
that both feed A and feed B have been disconnected before attempting
maintenance.
Caution
The hoses will
contain water. Use
care to avoid spills
in the unit.