A SERVICE OF

logo

Service Procedures: Assembly Site Form
18 InfraStruXure InRow RC
Environment: Yes/No
1. Is space construction complete
?
2. Is space environment suitable for unit operation?
Temp: Humid:
3. Is there signs of damage to the system (RC, CDU)?
4. If damage was present did the customer file a claim with the shipping
compan
y
for the dama
g
e?
5. Is there sufficient service access for the RC & CDU? (Minimum front
access is 36". The CDU Needs 36" on both sides as well for connection to
the Chilled Water mains durin
g
installation onl
y)
Front
A
ccess RC
:
Front Access
CDU:
6. Is there sufficient RC removal access (Minimum RC removal access
from the front of a row is 45"
)
Removal
A
ccess RC
:
Side Access
CDU:
7. Was equipment delivered inventoried against CTO report?
8.
Has an
y
shi
pp
ed loose missin
g
p
arts been re
p
orted to PC and ordered
?
9. Missing components list them here with expected ETA.
Description: Qty: ETA:
Installation Checks: Yes/No
1. Is the system located in the correct position per the CTO report
?
2. Has unit leveling feet been deployed?
3. Is Unit leveled?
4.
Is Unit properly attached to the rest of the cabinets of the ISX Solution
p
er the installation manual?
(
Document number 990-2402
)
5. Does the unit have to be mounted to the floor for Seizmic reasons
?
6. If Seizmic mounting is required has the shipping brackets been reused
to la
g
the RC and or CDU to the floor?
7. Does the RC have a RACS (Rack Air Containment System) attached to
the RC
(
Return or both Return and Suppl
y)
?
8.
Is the RACS installed properly per the Installation manual for the RACS
? (Document numbers 990-2643 RACS Overview, 990-2858 RC return,
990-2859 SX return, 990-2860 RACS end caps, 990-2861 RC supply, 990-
2863 SX front
)
9. Is the RC part of a HACS (Hot Aisle Containment System)
?
10. Is the RC installed into the HACS per the installation manual for the
HACS?
(
Document number 990-1607B
)
11. Is the RC piping connected to a CDU (Coolant Distribution Unit)?
12. Is the CDU installed per the installation manual? (Document number
990-2823
)
13. Is the RC and or CDU on a raised floor that can support the operational
weight of the units? (Operating weight of the RC 400lbs, Operational
wei
g
ht of the CDU is 525lbs
)
Mechanical Checks: Yes/No
1.
Has APC provided the Chiller?
2. Is a CDU and Pex-Al-Pex tubing being used
?
3. If Pex-Al-Pex tubing is being used is it supported every 32" or based on
local piping support requirements?
4. Has a 20 mesh strainer been installed in the Chilled Water supply main
to the CDU Unit or to the RC Suppl
y
line if the CDU is not used?
5. Which piping configuration is being used on the RC Top or Bottom? Top: Bottom:
PSIG:
7.
A
ny leaks present in the piping?
8. Is the Chilled water piping the proper size?
Su
pp
l
y
: Return:
Record piping sizes for Chilled Water mains
Comments:
APC Part Number:
Comments:
List missing parts below with Qty's and ETA
Comments:
6. Was the chilled water piping pressure tested?