Bosch Appliances D9412GV4 Video Gaming Accessories User Manual


 
Terminal
No
Terminal
Description
Requirements
16 POINT 4 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω.
17 POINT 5 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω.
18 POINT 5/6
COMMON
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω.
19 POINT 6 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω.
20 POINT 7 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω.
21 POINT 7/8
COMMON
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω.
22 POINT 8 Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω.
23 ZONEX
COMMON
22 AWG min (up to 14 AWG max)
24 ZONEX POWER 22 AWG min (up to 14 AWG max)
25 ZONEX IN 2* 22 AWG min (up to 14 AWG max)
26 ZONEX OUT 2* 22 AWG min (up to 14 AWG max)
27 ZONEX IN 1 22 AWG min (up to 14 AWG max)
28 ZONEX OUT 1 22 AWG min (up to 14 AWG max)
29 SDI COMMON Terminal accommodates 14 to 22 AWG, use appropriate wire size based on peripheral
device current.
30 SDI DATA
BUS B
22 AWG min (up to 14 AWG max)
31 SDI DATA
BUS A
22 AWG min (up to 14 AWG max)
32 SDI POWER Terminal accommodates 14 to 22 AWG, use appropriate wire size based on peripheral
device current.
33 SDI2 COMMON Terminal accommodates 14 to 22 AWG, use appropriate wire size based on peripheral
device current.
34 SDI2 DATA
BUS B
22 AWG min (up to 14 AWG max)
35 SDI2 DATA
BUS A
22 AWG min (up to 14 AWG max)
Control Panel Specifications | en 31
Bosch Security Systens, Inc. UL Installation Instructions 2012.12 | 02 | F.01U.265.462