Voltage Input
(Power Supply)
1
Primary: Terminals 1 and 2 16.5 VAC 40 VA class 2 plug-in
transformer (D1640)
Secondary: Terminals 4 and 5 Sealed lead-acid rechargeable battery
(12.0 VDC, 7 Ah or 12.0 VDC, 17.2 or 18
Ah). The control panel supports up to two
12.0 VDC, 7 Ah batteries using the D122/
D122L Dual Battery Harness or two
D1218 (12.0 VDC, 17.2 or 18 Ah)
batteries using a D122/D122L.
Current
Requirement
Control Panel: Idle 225 mA; Alarm 300 mA. Refer to the Current Rating
Chart for Standby Battery Calculations section in the D9412GV4/D7412GV4
v2.00 Installation and System Reference Guide (P/N: F01U265457) for the
current draw requirements of other system components.
Power Outputs
2
All external connections are power-limited except battery terminals
Continuous
Power
Outputs
Terminals 3,
24, 32, 36
1.4 A maximum at 12.0 VDC Nominal
(continuous supply) total for all devices
and outputs supplied at Terminals 3, 24,
32, and 36.
Alarm Power
Output
Terminals 6
and 7
2.0 A maximum at 12.0 VDC Nominal
output. Output can be steady or one of
four pulsed patterns depending on
programming. Refer to Outputs in RPS
Help.
Switched
Aux Power
Terminal 8 1.4 A maximum at 12.0 VDC Nominal
output. Continuous output is interrupted
by Sensor Reset, or alarm verification
depending on programming. Refer to
Outputs in RPS Help.
Fire and Fire/
Burglary
Systems
To comply with UL 985 and 864 listing standards for fire
alarm systems, the total combined continuous and alarm
current draw for the system during alarm conditions must
be limited to 1.4 A provided by the primary power supply
(rectified AC). If current draw for the system exceeds 1.4
A, use a UL Listed 12 VDC regulated, power limited
auxiliary power supply module such as the B520 (refer to
the Keyswitch Wiring section).
1
Requires a UL Listed power supply.
2
For UL 864 applications, refer to 6.0 Compatibilities for compatible devices.
Minimum
Operating
Voltage
10.2 VDC
SDI Bus SDI Bus A+: 9 VDC 15000 ft (4572 m) maximum
5
Control Panel Specifications | en 27
Bosch Security Systens, Inc. UL Installation Instructions 2012.12 | 02 | F.01U.265.462