Terminal 8
Terminal 8 provides continuous positive (+) 12.0 VDC Nominal power. Output C interrupts the
power at Terminal 8 when activated. Use Terminal 8 to power smoke detectors or other
devices that are reset by interrupting power. One self-resetting circuit breaker protects
Terminals 6, 7, and 8 against shorts.
Verification/Reset Output
The default program sets Output C (Terminal 8) as a verification and reset output. Refer to
Output Parameters and Point Assignments in the D9412GV4/D7412GV4 v2.00 Program Entry
Guide (P/N: F01U265459) for instructions on programming verification/reset outputs and
points.
Performing a sensor reset at a keypad produces a five-second output activation of verification/
reset outputs. The control panel ignores verification and reset points during the five-second
output activation.
4.6.4
26 en | Power Supply and Power Outputs Control Panel
2012.12 | 02 | F.01U.265.462 UL Installation Instructions Bosch Security Systens, Inc.