Honeywell wt6500 Video Gaming Accessories User Manual


 
14
SMARTBOX™ Controller for HONEYWELL™ Wind Turbine WT6500 Owner’s Manual - Rev14
SMARTBOX Installation
Turbine Over-current Protection
TheNECrequirestheturbinecircuittobeprotectedwithadeviceratedfor125%of
the rating of the circuit. The DC-rated fuse or circuit breaker between the turbine and
the SMARTBOX™ Controller must have a maximum size of 15 (the maximum current
rating of the SMARTBOX™ Controller).
SHOCK HAZARD OR FIRE HAZARD
Over-current protection must be installed to protect the
SMARTBOX™ Controller from short circuits and to provide
a means of disconnecting it. Failure to follow this warning
may result in death, personal injury or property damage.
REVERSE POLARITY DAMAGE
BeforemakingthenalDCconnectionorclosingtheDC
breaker or disconnect, check cable polarity at both the
battery and the SMARTBOX™ Controller. Positive (+)
must be connected to positive (+). Negative(-) must be
connected to negative (-). Failure to follow this warning may
result in death, personal injury or property damage.
TURBINE JUNCTION BOX
EARTH
GROUND
STAKE
TURBINE POLES
SEE TURBINE TO CONTROLLER SIZE
CHART ON SHEET 1
(2) #10 THWN-2 + #6 GND
¾” CONDUIT
MAX DISTANCE 3 FEET.
#4 GND
Figure 2.6 Turbine Circuit Diagram
TURBINE TO CONTROLLER WIRE SIZE CHART
TURBINE WIRE MAX DISTANCE (FT) EMT CONDUIT (INCH)
#10 (#6 GND) 3/4
#8 (#4 GND) 1
150
200