Toshiba V200 Video Game Console User Manual


 
Page 105
When COM ports are configured as Modbus slaves, the internal PLC tags are mapped to the modbus addresses as
given in the following table:
PLC Tag description Reg. Addressing
Bit
Addressing Modbus address
I/O register XW(400)
X
(6400) 440001 - 440400
YW(400) Y (6400) 441001 - 441400
Auxiliary registers BW00-BW255 B0000 to B4095 442001 - 442256
System Registers SW00-SW256 Not Mapped 420001 - 420256
Timer Registers T00-T255 Not Mapped 400001 - 400256
Counter Register C00-C255 Not Mapped 410001 - 410256
Data Registers D0000-D4095 Not Mapped 450001 - 454096
Retentive Registers Not Mapped 430001 - 431400
Index Register (I,J,K) I Not Mapped 443001
J Not Mapped 443002
K Not Mapped 443003
Configuration MW registers MW(1600) M(25600) 460001-461600
COILS:
TR0- TR15
Input Coil (R)
X
(6400) 000001 - 006400
Output Coil (R/W)
Y (6400) 010001 - 016400
System Coil (R/W)
S 0000 to S 0099 020001 - 020100
Internal Coil (R/W)
B 0000 to B 1023 030001 - 034096
Timer Devices (256 bits = 16 words)
T. 000 to T. 255 021001 - 021256
Counter Devices (256 bits = 16 words)
C. 000 to C. 255 022001 - 022256
Configuration MW coils
M(25600) 035001 - 060600