30
SMARTBOX™ Controller for HONEYWELL™ Wind Turbine WT6500 Owner’s Manual - Rev14
Operation
the energy consumption state (see the Fault and Troubleshooting section for complete
details):
Display- Display State Description
TURBINE FAULT
GFI
Turbine is stopped and contains a GFI fault.
TURBINE FAULT
NO WIND SPEED
Voltage sensed but Anemometer not sensing wind
speed.
TURBINE FAULT
TURBINE OVER CURRENT
Turbine is stopped and contains an over current fault.
TURBINE FAULT
TURBINE OVER VOLTAGE
Turbine is stopped and contains an over temperature
fault.
TURBINE FAULT
NO TURBINE
Anemometer is sensing wind speed but there is no
voltage sensed.
TURBINE FAULT
LOW BATT
Turbine is stopped and contains a low battery fault.
TURBINE FAULT
HIGH BATT
Turbine is stopped and contains a high battery fault.
TURBINE FAULT
OVER TEMP
Turbine is stopped and contains an over temperature
fault.
TURBINE FAULT
CHARGE OVER CURRENT
Turbine is stopped and contains an over current fault.
TURBINE FAULT
INVERTER NO OUTPUT
See Figure 4.4
TURBINE FAULT
INVERTER OVER
CURRENT
See Figure 4.4
Figure 4.3 Turbine Fault Stop States
• Turbine User Stop State
The turbine will enter its User Stop state if the user engages the manual stop
command in the technician’s menu accessible via the SMARTBOX™ Controller. When
the SMARTBOX™ Controller is in user mode, the turbine is immediately stopped.
While in user stop mode, no A/C will be produced so the inverter is shut off and the
transfer switch is switched back to the grid. The SMARTBOX™ Controller must be
placed in run mode before a charge cycle can start again.
Display - Stopped State Description
TURBINE STOPPED
PRESS ANY KEY
Turbine is stopped with no faults. Back light is off with
no information scroll.
System Protection
Cool Down
The turbine will shut off and begin cool down if the charger reaches or exceeds a
temperature of 125°c or/and the enclosure reaches or exceeds a temperature of 60°c.
The turbine will resume working after the charger temperature drops below 70°c and/
or the enclosure temperature drops below 45°c.
Over Wind Speed
The turbine will turn off when wind speed reaches 42mph or higher. It will resume
working after the wind speed drops to 35mph or lower.