A SERVICE OF

logo

Component Replacement: Condensate Pump
InfraStruXure InRow RC Service 47
7. Remove the T-20 screw securing the
condensate pump bracket to the top of the
power supply box and remove the bracket
from the box.
8. Slide the condensate pump up and out the
bottom of the bracket.
9. Insert the new pump into the existing
bracket, and reverse this procedure to
install it. Tighten the T-20 screw securing
the pump bracket to the power supply box
to 15–20 in·lb (1.7–2.3 N·m).
10. Verify operation of the condensate pump.
11. Replace covers, filter, doors and panels, and
return the unit to service.
Caution
Verify that the correct pump is
installed for this application.
Condensate Pump Identification
SKU Unit Voltage Replacement part number
ACRC100 120V W0M-61038
ACRC101 230V W0M-61044
ACRC103 230V W0M-61044