Trane Zone Controller Video Game Controller User Manual


 
Diagnostics
CNT-SVX07C-EN 61
Generic AIP Failure Invalid or missing value
for generic analog input
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Informational
Local Fan Mode Failure Invalid or missing fan-
speed switch (reverts to
default fan speed)
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Automatic
Local Setpoint Failure Invalid or missing value
for zone temperature set-
point (reverts to default
setpoint)
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Automatic
Generic Temperature Failure Invalid or missing
generic temperature
value
Fan unaffected
Valves unaffected
Outdoor air damper unaffected
Face and bypass damper unaffected
DX cooling/electric heat unaffected
Baseboard heat unaffected
Informational
Invalid Unit Configuration Software is configured
improperly
Fan off
Valves off
Outdoor air damper closed
Face and bypass damper closed
DX cooling/electric heat off
Baseboard heat off
Manual
Normal On start-up Fan unaffected
Valves unaffected
Electric heat unaffected
Compressors unaffected
Damper unaffected
Automatic
Table 16. Diagnostics (Continued)
Diagnostic Probable cause Consequences
Diagnostic
type