Trane CNT-SVX07C-EN Video Game Controller User Manual


 
Manual output test
CNT-SVX07C-EN 53
Table 11. Manual output test sequence for non-face-and-bypass configurations
Step Result BOP1 BOP2 BOP3 BOP4 BOP5 BOP6 BOP7 BOP8 BOP9 BOP10
Number of times
Test button is pressed
Fan high
1)Fan medium
2)Exhaust
Fan low
1)Cooling/changeover
valve, open
2)Two-position cooling/
changeover valve
3)DX compressor
Cooling/changeover
valve, close
1)Heating valve, open
2)Two-position heat valve
3)Electric heat, stage 1
1)Heating valve, close
2)Electric heat, stage 2
Outdoor air damper, open
Outdoor air damper, close
1)Generic
2)Baseboard heat
1 Begins test
mode
1
OffOff OffOff On/Close Off 1) On/Close
2) Off
Off On/Close Off
2
Fan high
2
On/High Off Off Off Off Off Off Off Off Off
3Fan
medium
3
Off 1) On/Med
2) Off
Off Off Off Off Off Off Off Off
4
Fan low
4
Off Off On/Low Off Off Off Off Off Off Off
5 Main open,
DX on
On/High Off Off On/Open Off Off Off Off Off Off
6 Main close,
DX off, aux
open, EH1
on
On/High Off Off Off On/Close On/Open Off Off Off Off
7 Aux open,
EH1 on,
exhaust
fan
5
On/High 1) Off
2) On
Off Off Off On/Open Off Off Off Off
8 Aux close,
EH1 off,
EH2 on,
damper
open
On/High Off Off Off Off Off On/Close On/Open Off Off
9Damper
close
On/High Off Off Off Off Off Off Off On/Close Off
10 Generic/
baseboard
heat
energized
6
On/High Off Off Off Off Off Off Off Off On