Mitsubishi Electronics FX2NC Video Game Controller User Manual


 
FX2NC Series Programmable Controllers Introduction 1.
1-25
Judgment (Example)
a) 5V DC control current capacity check
b) Input/output point connection upper limit check
Calculation result:
The 5V DC power total current consumption value and total input/output points are in the
specified ranges, therefore the above system configuration is possible.
5V DC current capacity of main unit
(value shown in Sec. 1.5.2): 560 mA
Total current consumption of all connected blocks
(value written in calculation form): 475 mA
OK
nr
Input point connection
upper limit : 184 points
Input points of main unit
(value shown in Sec. 1.5.2):
16 points
Total input points of all
connected blocks (value
written in calculation form):
48 points
+ =
64
points
Output point
connection upper limit:
184 points
Output points of main unit
(value shown in Sec. 1.5.2):
16 points
Total output points of all
connected blocks (value
written in calculation form):
80 points
+ =
96
points
Input/output point
connection upper limit:
256 points
Input/output points of main unit
(value shown in Sec. 1.5.2):
32 points
Total input/output points of all
connected blocks (value
written in calculation form):
152 points
+ =
184
points
OK
OK
OK
o
p
q
s
t
v