Mitsubishi Electronics FX2NC Video Game Controller User Manual


 
FX2NC Series Programmable Controllers Introduction 1.
1-19
*1:Maximum number of I/O points per system Connection is allowed as far as the following
condition is satisfied:
(Actual number of I/O points of PLC) + (Number of points occupied by special extension
blocks) + (Number of points occupied by FX
2N
-16CCL-M: 8) + (32 x Number of remote I/O
modules)
256
*2:For details, refer to the FX
2N
-64CL-M user’s manual.
*3:Value depends on the switch setting (16, 32, 48, 64, 96 or 128 points).
*4:Maximum of 1 unit can be connected.
MODEL
CURRENT CONSUMPTION
5V DC
INPUT
X
OUTPUT
Y
TOTAL
X/Y
FX
2N
-16CCL-M - *1 8 *1 8
FX
2N
-32CCL 130mA - 8 - 8
FX
2N
-64CL-M 190mA *2 8 *2 *2
FX
2N
-16LNK-M 200mA *3 *3 *3 *3
FX
2N
-10GM - - 8 - 8
FX
2N
-20GM - - 8 - 8
FX
2N
-1RM-E-SET
*4
--8-8
FX
0N
-232ADP 200mA - - - -
FX
2NC
-232ADP 100mA - - - -
FX
0N
-485ADP 30mA - - - -
FX
2NC
-485ADP 150mA - - - -
FX-2PIF 290mA - - - -