Series
Fan-Powered
CONFIDENTIAL DOCUMENT. FOR INTERAL USE ONLY. 58VAV-SLM005-EN
Performance
Data—Hot Water
Coil (I-P)
Titus—Fan Size 6 (I-P)
Water
Pressure Airflow (Cfm)
Rows Gpm Drop (ft) 1300 1440 1580 1720 1860 2000 2140 2280 2420
1-Row 1.0 .40 31.7 32.7 33.6 34.4 35.2 35.8 36.5 37.0 37.6
Capacity 2.0 1.3 39.8 41.5 43.1 44.5 45.9 47.1 48.3 49.3 50.4
MBH 4.0 4.3 45.5 47.9 50.0 52.0 53.9 55.6 57.3 58.9 60.3
6.0 8.8 47.9 50.4 52.8 55.1 57.2 59.2 61.1 62.9 64.6
2-Row 1.0 .80 47.3 48.3 49.2 50.0 50.6 51.2 51.7 — —
Capacity 2.0 2.6 66.2 68.8 71.1 73.2 75.0 76.7 78.3 — —
MBH 4.0 9.0 80.2 84.4 88.3 91.8 95.1 98.2 101.0 — —
5.0 13.4 83.5 88.1 92.4 96.4 100.1 103.6 106.8 — —
Titus—Fan Size 7 (I-P)
Water
Pressure Airflow (Cfm)
Rows Gpm Drop (ft) 1500 1650 1800 1950 2100 2250 2400 2550 2700
1-Row 1.0 .40 33.1 34.0 34.9 35.6 36.3 36.9 37.5 38.0 38.5
Capacity 2.0 1.3 42.2 43.8 45.3 46.7 47.9 49.1 50.2 51.2 52.2
MBH 4.0 4.3 48.8 51.0 53.1 55.0 56.8 58.5 60.1 61.7 63.1
6.0 8.8 51.5 54.0 56.3 58.5 60.6 62.5 64.4 66.1 67.8
2-Row 1.0 .80 48.7 49.6 50.4 51.0 51.6 52.1 52.5 52.9 —
Capacity 2.0 2.6 69.8 72.2 74.3 76.1 77.9 79.4 80.8 82.1 —
MBH 4.0 9.0 86.1 90.1 93.7 97.1 100.2 103.1 105.9 108.4 —
5.0 13.4 90.0 94.5 98.6 102.4 105.9 109.2 112.4 115.3 —