Night setback
Night setback
Select:
Cursor Content
Main menu:
Night setback No / Yes
Temp. range 12 - 28
Start 23:00
Stop 5:00
Night setback No / Yes
Temp. range 12 - 28
Start 23:00
Stop 5:00
Changes saved
Move the cursor to the desired item with the F1
or F2 button out of Night setback No (disable)/
Yes (enable), Temp. range, Start time, or Stop
time.
Change the settings with the F3 or F4 button.
•
Temp. range:
The lower limit temperature (for
heating operation) and the
upper limit temperature (for
cooling operation) can be set.
The temperature difference
between the lower and upper
limits must be 4
ºC (8ºF) or
more. The settable temperature
range varies depending on the
connected indoor units.
•
Start/Stop time:
settable in 5-minute increments
* Press and hold the button to rapidly advance
the numbers.
Press the SELECT button to save the settings.
A confirmation screen will appear.
41
Cool
Room
AutoSet temp.
Mode Temp. Fan
Fri
will appear on the Main display in the
Full mode when the Night setback function is
enabled.
The Night setback will not work in the following cases:
when the unit is in operation, when the Night setback
function is disabled, during an error, during check (in the
service menu), during test run, during remote controller
diagnosis, when the clock is not set, during Function
setting, when the system is centrally controlled (On/Off
operation or temperature setting from local controller is
prohibited).
Navigating through the screens
• To go back to the Main menu .......... MENU button
• To return to the previous screen ...... RETURN button