A SERVICE OF

logo

Operation
2–24 152379 Rev C
Energize Procedure (Startup)
To start up the PV100S:
1. Remove any lockout devices from the utility connection circuit breaker and
PV disconnect switch.
2. Close the utility connection circuit breaker.
3. Close the AC Disconnect Switch.
4. Close the DC Disconnect Switch.
5. Turn the O
N/OFF switch to the ON position.
After a 15 second initialization period, the PV100S will automatically transition
to ‘Waking Up’, given the PV voltage is greater than the PV V Start set point.
De-Energize/Isolation Procedure (Shutdown)
The following procedure should be followed to de-energize the PV100S for
maintenance.
To isolate the PV100S:
1. Turn the
ON/OFF switch to the OFF position.
2. Open the DC interface disconnect switch.
3. Open the AC interface disconnect switch.
4. Open the utility connection circuit breaker.
5. Install lockout devices on the utility connection circuit breaker and DC
disconnect switch.
WARNING
The terminals of the DC input may be energized if the PV arrays are energized. In
addition, allow 5 minutes for all capacitors within the main enclosure to discharge after
disconnecting the PV100S from AC and DC sources.