Introduction
1–6 152379 Rev C
Physical Characteristics
The PV100S comes in two modules comprised of six enclosures to house the
electronics described above. The first module includes the Main Inverter
Enclosure, Inductor Enclosure, DC Interface Enclosure, and Communications
Enclosure. The second module includes the Transformer Enclosure and AC
Interface Enclosure.
These components are identified in Figure 1-2.
Figure 1-2
PV100S Major Components
WARNING:
This is a class A product.
In a domestic env ir onment this
product may cause radio
interferences, in which case, the user
may be required to take adequat e meas ures.
0
I
^
F2654
32
.
-
1
0
F3MENU
F4ENTER
987 F1
^
DISCONNE CT
PV
U
L
®
TYPE 3R
61CN
LISTE D UT ILITY I NT ERACTI V E PHASE I NVERTE R
Mfg - Arl
Max. system DC
Vo lt ag e 6 00V
Max. oper ating
current 319A
Rang e of oper.
Volts . 330-480V
Max. array abort
circuit current
480A
Nominal output
voltage 208V
Maximum utility
feedba ck cu rrent
178A
Max. inp ut
current 3A
Oper. Volt. Range
183-229 L -L
Oper. Freq. range
59.3 - 60.5
Norm a l output frequency
60 Hz
Max. output
overc urr ent
protection
400A
Maximum output
fault current
323 A
DC
DC
DC
DC
DC
DC
DC
AC
AC
AC
AC
AC
AC
AC
Max. continuo us
output current
278A
Max cont inuous
output power
100 kVA
Maximum operating ambient 50 °C
MODEL NUMBER:
PV100S-20 8
SERIAL N UM BE R:
XXXX
L-152 462 Rev A
MANUFACTURED
04
05
06
07
JAN
FEB
APR
MAR
MAY
JUN
JUL
AUG
SEP
OCT
NOV
DEC
THIS UNIT EMPLOYS FI EL D AD JU ST AB LE VO LTAG E AN D
FREQ U EN C Y SET POI NT S AN D TIME DELAYS. THEY ARE
FACTORY SET IN COMPLIANCE WITH UL1 741 A ND MAY
ONLY BE CHANGED BY TRAINED SERVICE TECHNICIANS
WIT H AP PR OVAL BY BOTH TH E LO CAL UT ILITY AND
EQUIPM EN T O W NE R.
REFER TO TH E OPERATOR’S
MANUAL FOR FU RT HE R D E T AI L.
WARNING
RISK OF ELECTRICAL SHOCK
DO NOT REMOVE COVER,
NO USER SERVICEABLE
PARTS INSIDE,
STORED ENERG Y IN CAPACITOR.
ALLOW AT LEAST 5 MINUTES
AFTER DISCONNECTING ALL
SOURCES OF SUPPLY.
REFER SERVICING TO QUALIFIED SERVICE
PERSONNEL.
BOTH AC AND DC VOLTRAGE SOURCES ARE
TERMINAED
INSIDE THIS EQUIPMENT.
EACH CIRCUIT MUST BE
INDIVIDUAL DISCONNECTED
BEFORE SERVICING.
WHEN THE PHOTOVOLTAIC ARRAY
IS EXPOSED TO LIGHT,
IT SUPPLIES A DC VOLTAGE
TO THIS EQUIPMENT.
Main Inverter
Enclosure
DC Interface
Enclosure
Inductor
Enclosure
Transformer
Enclosure
AC Interface
Enclosure
Power Electronics Matrix
Communications
Enclosure