—7—
* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26.
If other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than
10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time-delay fuse or circuit breaker.
†† Start assist capacitor and relay required when using liquid solenoid valve or hard shutoff TXV (except 036 and 042, Series A; 048 and 060, Series A/B
single phase; and all 3-phase units). Do not use hard shutoff TXV with liquid solenoid valve.
‡‡ Use with low-ambient controller.
*** Fan motor with ball bearings required.
N/A—Not Applicable
NOTES:
1. All motors/compressors contain internal overload protection.
2. Copper wire must be used from service disconnect to unit.
3. Control circuit is 24v on all units and requires external power source.
ACCESSORY USAGE GUIDELINE
* For tubing line sets between 50 and 175 ft, refer to Residential’s Split Systems Long-Line Application Guidelines.
† Only when low-pressure switch is used.
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
1. Ball Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.
2. Coastal Filter
A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.
SUGGESTED USE: In geographic areas where salt damage could occur.
3. Compressor Start Assist—Capacitor/Relay Type
Start capacitor and start relay which gives ‘‘hard’’ boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.
Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil.
Installations where Liquid-Line Solenoid Valve has been added.
4. Compressor Start Assist—PTC Type
Solid-state electrical device which gives a ‘‘soft’’ boost to compressor motor at each start-up.
SUGGESTED USE: Installations with marginal power supply.
Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.
5. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication
on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 50 ft.
When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with Low-Ambient Controller.)
All commercial installations.
6. Cycle Protector
Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has
been interrupted for any reason, including normal room thermostat cycling.
SUGGESTED USE: Installations in areas where power interruptions are frequent.
Where user is likely to ‘‘play’’ with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
High-rise applications.
7. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: All units where Winter Start Control has been added.
8. Filter Drier
A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow.
SUGGESTED USE: All split-system units.
ACCESSORY
REQUIRED FOR
LOW-AMBIENT
APPLICATIONS
(Below 55°F)
REQUIRED FOR
LONG-LINE
APPLICATIONS*
(Over 50 Ft)
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 Miles)
Crankcase Heater Yes Yes No
Evaporator Freeze Thermostat Yes No No
Winter Start Control Yes† No No
Accumulator No No No
Compressor Start Assist
Capacitor and Relay
Yes Yes No
Low Ambient Controller
or
MotorMaster® Control
Ye s N o No
Wind Baffle See Low-Ambient Instructions No No
Coastal Filter No No Yes
Support Feet Recommended No Recommended
Liquid-Line Solenoid Valve
or
Hard Shutoff TXV
No
See Long-Line
Application
Guideline
No
Ball Bearing Fan Motor Yes No No