8. Special I/O Functions
Operation
Pulse enable
Frequency setting
+
Frequency
Pulse output
-
Sample program
In this example, 3 (H0003) is set in SW26. As a result, the CW/CCW mode pulse output
function is selected.
When R000 is ON, the pulse output is started with the frequency designated by D0100.
If an invalid frequency is designated, the frequency setting error flag (S26F) comes ON
and the pulse enable flag (S270) is turned OFF. Then the pulse output is stopped.
-300-1000
3001000
100
-100
1kHz
300Hz
100Hz
300Hz
100Hz
1kHz