Toshiba PROSEC T1 T1S Video Game Controller User Manual


 
6F3B0250
Basic Hardware and Function
177
7. Instructions
FUN 056 MAVE Moving average
Expression
Input
-
[
A
MAVE (
n
)
B
®
C
]
-
Output
Function
When the input is ON, this instruction calculates the average value of the latest
n
scan’s register
A
data, and stores it in
C
. The allowable range of
n
is 1 to 64.
This instruction is useful for filtering the analog input signal.
The latest
n
scan’s data of
A
are stored in
n
registers starting with
B
, and
C+1
are used as pointer.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution ON
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Input data
ÖÖÖÖÖÖÖÖÖÖ Ö
n
Data size 1 - 64
B
Start of table
ÖÖÖÖÖÖ
C
Output data
ÖÖÖÖÖÖÖÖ
Example
The latest 5 scan’s data of XW04 is stored in D0900 to D0904 (5 registers), and the average value
of them is calculated and stored in D0010.
D0011 is used as internal work data.
XW04 D0010
1st scan 1000 200 = (1000) / 5
2nd scan 1005 401 = (1000 + 1005) / 5
3rd scan 1009 603 = (1000 + 1005 + 1009) / 5
4th scan 1012 805 = (1000 + 1005 + 1009 + 1012) / 5
5th scan 1007 1006 = (1000 + 1005 + 1009 + 1012 + 1007) / 5
6th scan 1004 1007 = (1005 + 1009 + 1012 + 1007 + 1004) / 5
7th scan 998 1006 = (1009 + 1012 + 1007 + 1004 + 998) / 5
8th scan 994 1003 = (1012 + 1007 + 1004 + 998 + 994) / 5
T1S only