Nailor—Fan Size 7 (I-P)
Water
Pressure Airflow (Cfm)
Rows Gpm Drop (ft) 1300 1600 1900 2200 2500 2800 3100 3400
1-Row 1 0.13 31.2 32.1 34.5 35.9 36.3 37.3 37.8 38.0
Capacity 2 0.48 41.2 44.8 47.1 49.0 51.2 52.7 53.9 55.5
MBH 4 1.9 48.2 53.1 57.5 61.2 63.8 66.3 68.4 71.2
5 2.9 51.2 56.0 60.1 63.9 67.5 70.9 73.1 75.7
7.5 6.0 53.5 58.4 63.8 68.0 72.5 76.1 78.3 81.1
2-Row 1 0.1 40.0 42.1 43.2 44.2 45.0 45.8 46.2 47.1
Capacity 2 0.28 57.6 62.4 66.1 68.6 71.1 72.7 74.8 76.2
MBH 4 1.1 72.5 80.1 87.1 92.5 97.4 101.2 105.0 108.2
5 1.7 77.1 85.8 92.7 99.2 104.7 109.8 113.78 117.6
7.5 3.5 82.5 92.6 101.9 108.8 116.2 123.0 128.8 133.7
Note: Size 2 and 3, 1-row coils are single-circuit. Size 4–7, 1-row coils are multi-circuit. All 2-row coils are multi-
circuit.
Nailor—Fan Size 6 (I-P)
Water
Pressure Airflow (Cfm)
Rows Gpm Drop (ft) 1000 1200 1400 1600 1800 2000 2200
1-Row 1 25.9 27.5 28.9 29.8 30.5 31.3 31.9
Capacity 2 32.4 34.8 36.9 38.6 40.2 41.6 42.8
MBH 4 36.8 40.0 42.9 45.4 47.6 49.6 51.3
5 37.9 41.3 44.5 45.4 49.4 51.7 53.6
7.5 39.4 43.1 46.8 49.2 52.1 54.6 56.8
2-Row 1 0.18 35.2 37.4 38.7 39.8 41.0 32.0 32.5
Capacity 2 0.7 37.5 51.3 54.8 57.0 59.5 61.9 63.0
MBH 4 2.7 57.4 63.0 67.9 72.5 36.2 79.9 82.6
5 4.0 59.9 66.2 71.5 76.2 80.9 84.9 88.0
7.5 8.5 63.6 70.2 76.3 82.4 87.5 92.0 96.3
Performance
Data—Hot Water
Coil (I-P)