27VAV-SLM005-EN
Parallel
Fan-Powered
Performance
Data—Hot Water
Coil (I-P)
ETI—Fan Sizes 0404, 0504, 0604, 0804, 0806, 0811 (I-P)
Airflow (Cfm)
Rows Gpm WPD (ft) 200 300 400 500 600 700 800
1-row 0.5 0.4 10.74 12.81 14.25 15.31 16.12 16.73 17.21
Capacity 1 1.2 12.50 15.51 17.81 19.64 21.16 22.44 23.53
MBH 2 4.2 13.60 20.89 20.25 22.71 24.83 26.68 28.33
3 8.8 14.02 17.99 21.22 23.96 26.34 28.45 30.34
5 22.1 — 18.59 22.07 25.06 27.69 30.05 32.31
2-row 0.5 0.1 13.92 16.60 18.32 ————
Capacity 1 0.3 — 21.37 24.65 27.19 29.21 30.86 32.21
MBH 2 1.2 — — — 33.3 36.62 39.45 41.92
3 2.5 ————39.88 43.32 46.38
5 6.2 —————46.97 50.64
ETI—Fan Sizes 1006, 1018, 1211, 1218, 1221 (I-P)
Airflow (Cfm)
Rows Gpm WPD (ft) 400 600 800 1000 1200 1400 1600 1800
1-row 0.5 0.5 16.33 18.56 19.91 20.73 ————
Capacity 1 1.6 20.62 24.72 27.64 29.84 31.55 32.92 34.01 34.88
MBH 2 5.5 23.56 29.25 33.62 37.15 40.11 42.62 44.81 46.72
3 11.3 24.73 31.10 36.14 40.13 43.87 46.96 49.70 52.14
5 28.2 25.74 32.75 38.42 43.21 47.36 51.03 54.32 57.30
2-row 0.5 0.1 20.24 — — — ————
Capacity 1 0.5 27.44 32.90 36.51 39.05 40.88 42.21 43.18 43.86
MBH 2 1.6 — 41.49 47.98 53.05 57.15 60.54 63.37 65.78
3 3.2 — — 53.24 59.73 65.17 69.81 73.82 77.33
5 8.0 — — — 66.22 73.11 79.14 84.49 89.29
ETI—Fan Sizes 1411, 1418, 1424, 1621, 1624 (I-P)
Airflow (Cfm)
Rows Gpm WPD (ft) 1000 1200 1400 1600 1800 2000 2200
1-row 0.5 0.621.69——————
Capacity 1 1.8 31.45 33.28 34.74 34.01 36.85 37.61 38.21
MBH 2 6.3 39.38 42.56 45.27 47.63 49.69 51.52 53.15
3 12.8 42.81 46.66 50.01 52.98 55.63 58.02 60.20
5 31.2 45.96 50.47 54.47 58.05 61.31 64.28 67.02
2-row 0.5 — ———————
Capacity 1 0.6 40.59 42.53 43.96 45.00 45.75 — —
MBH 2 1.8 55.45 59.82 63.44 66.47 69.04 7125 73.15
3 3.7 62.55 68.38 73.36 77.67 81.45 84.78 87.76
5 9.1 69.45 76.86 83.36 89.15 94.34 99.04 103.32
Notes:
1. Data is based on entering water temperature of 180°F and entering air temperature of 65°F.
2. Water Coil located on plenum inlet.