A SERVICE OF

logo

Features and Specifications
Specifications
18 Operating Manual for RS-232 for XHR/XFR Series Power Supply
Table 1.6
Specifications for XHR 1000 W Series Supply with RS-232 Interface Installed (100 V to 600 V)
Models 100-10 150-7 300-3.5 600-1.7
Program Resolution
Voltage
Current
OVP
15.5mV
1.5mA
15.5mV
23.2mV
1.0mA
23.2mV
46.4mV
0.5mA
46.4mV
92.7mV
0.3mA
92.7mV
Program Accuracy
1
Voltage
Current
OVP
1. Apply accuracy specifications according to the following voltage program accuracy example:
Set a model 20-50 power supply to 10 volts.
The expected result will be within the range of 10 volts ± 50mV ± 0.12% of the set voltage of 10 volts.
150mV
±0.35%
80mA
±0.1%
1.0V
225mV
±0.35%
80mA
±0.1%
1.5V
225mV
±0.35%
80mA
±0.1%
3.0V
300mV
±0.35%
75mA
±0.1%
6V
Readback Resolution
Voltage
Current
15.5mV
1.5mA
23.2mV
1.0mA
46.4mV
0.5mA
92.7mV
0.3mA
Readback Accuracy
1
Voltage
Current
150mV
±0.35%
80mA
±0.1%
225mV
±0.35%
80mA
±0.1%
225mV
±0.35%
80mA
±0.1%
300mV
±0.35%
75mA
±0.1%