32
Parallel
Fan-Powered
VAV-SLM005-EN CONFIDENTIAL DOCUMENT. FOR INTERAL USE ONLY.
Performance
Data—
Electric Coil
Fan Electrical Performance
Max FLA
Fan Si ze HP 120 V 208 V 277 V
2 1/6 4.8 1.8 1.5
3 1/4 5.8 3.6 1.8
4 1/3 6.2 4.1 2.0
5 1/2 10.1 6.5 3.3
6, 7 3/4 13.4 8.4 4.5
Note: DIFFERENT motors than series units.
Information listed is at high speed)
35PE Nailor Electric Coil kW Guidelines—Minimum to Maximum
Fan Single-Phase Voltage Three-Phase Voltage
Size Stages 208 V/240 V 277 V 347 V 480 V 208 V 480 V 575 V
2 1 0.5–7.0 0.5–7.0 — — 0.5–7.0 0.5–7.0 —
(150–540 cfm) 2 0.5–7.0 0.5–7.0 — — 0.5–7.0 0.5–7.0 —
3 0.5–7.0 0.5–7.0 — — 0.5–7.0 0.5–7.0 —
3 1 0.5–8.0 .05–11.5 — — .05–11.5 .05–11.5 —
(150–775 cfm) 2 0.5–8.0 .05–11.5 — — .05–11.5 .05–11.5 —
3 0.5–8.0 .05–11.5 — — .05–11.5 .05–11.5 —
4 1 0.5–8.0 .05–11.5 — — 0.5–14.5 .05–16.0 —
(650–1080 cfm) 2 0.5–8.0 .05–11.5 — — 0.5–14.5 .05–16.0 —
3 0.5–8.0 .05–11.5 — — 0.5–14.5 .05–16.0 —
5 1 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–20.5 —
(590–1400 cfm) 2 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–20.5 —
3 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–20.5 —
6 1 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–25.0 —
(860–1670 cfm) 2 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–25.0 —
3 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–25.0 —
7 1 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–28.0 —
(1050–2185 cfm) 2 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–28.0 —
3 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–28.0 —