Fan Electrical Performance
Max FLA
Fan Size HP 120V 208V 277V
2 1/10 3.3 2.0 1.0
3 1/4 5.8 3.6 1.8
4 1/3 6.2 4.1 2.0
5 1/2 10.1 6.5 3.3
6 3/4 13.4 8.4 4.5
7 2@1/2 20.2 13.0 6.6
35SE Nailor Electric Coil W Guidelines—Minimum to Maximum
Fan Single-Phase Voltage Three-Phase Voltage
Size Stages 208V/240V 277V 347V 480V 208V 480V 575V
2 1 0.5–7.0 0.5–7.0 — — 0.5–7.0 0.5–7.0 —
(150–540 cfm) 2 0.5–7.0 0.5–7.0 — — 0.5–7.0 0.5–7.0 —
3 0.5–7.0 0.5–7.0 — — 0.5–7.0 0.5–7.0 —
3 1 0.5–8.0 .05–11.5 — — .05–11.5 .05–11.5 —
(150–775 cfm) 2 0.5–8.0 .05–11.5 — — .05–11.5 .05–11.5 —
3 0.5–8.0 .05–11.5 — — .05–11.5 .05–11.5 —
4 1 0.5–8.0 .05–11.5 — — 0.5–14.5 .05–16.0 —
(650–1080 cfm) 2 0.5–8.0 .05–11.5 — — 0.5–14.5 .05–16.0 —
3 0.5–8.0 .05–11.5 — — 0.5–14.5 .05–16.0 —
5 1 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–20.5 —
(590–1400 cfm) 2 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–20.5 —
3 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–20.5 —
6 1 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–32.5 —
(860–1670 cfm) 2 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–32.5 —
3 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–32.5 —
7 1 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–32.5 —
(1050–2185 cfm) 2 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–32.5 —
3 0.5–8.0 .05–11.5 — — 0.5–14.5 0.5–32.5 —
Notes:
1. Analog electronic controls are limited to maximum 2 stages.
2. Discharge air temperature may not exceed 120°F.
3. A minimum airflow of 70 cfm per kW is required for any given terminal in order to avoid possible nuisance tripping of the thermal cutouts.
Performance
Data—
Electric Coil