48049-136-05 Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012 Appendix A—Register List
© 1999–2012 Schneider Electric All Rights Reserved
37-EN
ENGLISH
TU_BATT_PCT Trip Unit % Battery 1 8843 PM % Unity
TU_SN Trip Unit Serial Number 4 8700 PM ASCII text
TUCommStatus Trip Unit Internal Comms Status 1 552 BCM Bit 11; ON = not responding, OFF = OK
*
For register entries that are not listed, please refer to the Micrologic device type register list. Contact your local sales office.
BCM = Circuit breaker communication module. CCM = Cradle communication module. PM = Trip unit protection module.
3-register date/time format: register 1: month (byte 1) = 1–12, day (byte 2) = 1–31; register 2: year (byte 1) = 0–199 (add to 1900 to determine the actual year), hour
(byte 2) = 0–23; register 3: minutes (byte 1) = 0–59, seconds (byte 2) = 0–59. Note: Bits 14 and 15 of the month/day register must be masked.
**
Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = –9,999 to +9,999). Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1]
+ R1. Range is zero to 9,999,999,999,999,999.