Parameter list for Bakery Models including: -
PRO 16DR, PRO 16VE, PRO 24VE, DR 16VE and DR 24VE.
PRO 20DR, PRO 40DR. Adjust parameter ‘SPL’ to ‘-5’, ‘SPH’ to ‘10’, ‘SP’ to ‘-4’ and ‘FDD’ to ‘-8’
Mnem. Definition Min. Max Default Dim.
Pro 16
Pro 24
DR 16
DR 24
SCL
Readout scale 1°C; 2°C; °F 2 flag 2
SPL
Minimum setpoint [ I ] -40 SPH 1 °C
-4
SPH
Maximum setpoint [ I ] SPL 40 3 °C
-4
SP
Setpoint [ I ] SPL SPH 2 °C
-4
HYS
Thermostat hysteresis [ I ] 0.1 10 3 °K
2
CRT
Minimum compressor rest time 0 30 2 min.
2
CT1
Compressor run with T1 failure 0 30 7 min.
7
CT2
Compressor stop with T1 failure 0 30 3 min.
3
2CD
Start delay 2nd compressor 0 120 0 sec.
0
DFR
Defrost frequency / 24h 0 24 2 1/24h
3
DLI
Defrost end temperature -40 40 20 °C
20
DTO
Maximum defrost duration 1 120 20 min.
20
DTY
Defrost type OFF; ELE; GAS OFF flag GAS
DRN
Drain down time 0 30 2 min.
2
DDY
Defrost display control 0 60 10 min.
10
FID
Fan activity during defrost NO YES YES flag
NO
FDD
Fan re-start delay temperature -40 40 0 °C
8
FTO
Evaporator fan maximum time-out 0 120 3 min.
3
FTC
Evaporator fan timed control NO YES YES flag
YES
FT1
Fan stop delay 0 180 15 sec.
15
FT2
Timed fan stop 0 30 2 min.
2
FT3
Timed fan run 0 30 1 min.
1
ATL
Low alarm differential -12 0 -5 °K
-5
ATH
High alarm differential 0 12 5 °K
5
ATD
Alarm Temperature Delay 0 120 90 min.
90
AHT
Condenser Alarm Temperature 0 75 60 °C
60
AHM
Condenser high temp. alarm operation NON; ALR; STP NON flag NON
ACC
Condenser cleaning period 0 52 0 wks
0
HDS
Sensitivity function eco / heavy duty 1 5 3 flag
3
IISM
2nd parameter set switching mode NON; MAN; HDD; DI2 HDD flag HDD
IISL
Minimum 2nd temp. set -40 IISH 1 °C -4
IISH
Maximum 2nd temp. set IISL 40 3 °C -4
IISP
Effective 2nd temperature set point IISL IISH 1 °C -4
IIHY
Hysteresis 2nd temperature set 0.1 10 3 °K 2
IIFT
Evap. fan timed control in mode 2 NO YES NO flag NO
IIDF
Defrost Frequency / 24h in mode 2 0 24 4 1/24h 6
SB
Button 0/1 enabling NO YES YES flag YES
DS
Door switch enabling NO YES YES flag NO
CSD
Compressor stop delay from door opening 0 30 1 min. 1
ADO
Door alarm delay 0 30 8 min. 5
D12
Function digital input D12 NON; HPS; IISM; RDS NON flag NON
LSM
Light switch mode NON; MAN; DOR NON flag NON
OAU
Control of AUX output NON; 0-1; LGT; 2CU; 2EU; ALR NON flag NON
OS1
T1 (air) probe offset -12 12 0 °K 0
T2
T2 (evap.) probe enabling NO YES NO flag YES
OS2
T2 (evap.) probe offset -12 12 0 °K 0
T3
T3 (cond.) probe enabling NO YES NO flag NO
OS3
T3 (cond.) probe offset -12 12 0 °K 0
T4
T4 (aux.) probe enabling NON; 2CU; 2EU NON flag NON
OS4
T4 (aux.) probe offset -12 12 0 °K 0
TLD
Delay for min./max. temp storage 1 30 5 min. 5
SIM
Display slowdown 0 100 3 exp. 3
ADR
Unit peripheral address 1 255 1 exp. 1