A3.1.6.4 Setup menu (SEt)
The Setup menu contains dispenser configuration settings that are typically not often reset after initial startup
of the dispenser.
A3.1.6.5 Test menu (tSM)
The Test menu contains Prime/Test Pump and other diagnostic test functions.
Parameter
name
Display
visualiza-
tion
Family
Nr.
Parameter
Nr.
Parameter description Unit of
measure
Min Max Factory set-
ting [for WT44]
Detergent
manager
dtM
10 0 Detergent Manager monitors the probe
controlled detergent feed time to reach
set point. When the detergent feed time
exceeds 150% of the setup feed time
during a 12 hour period, Detergent
Manager automatically disables probe
detergent control and enables timed
detergent control. This function is only
available when Probe detergent control is
chosen in “Operatinion mode” (OPM)
parameter on Startup Family.
“0”: Detergent manager off.
“1”: Detergent manager on.
-01 1
Rinse
manager
riM
10 1 Rinse Manager shuts off the rinse pump
when the rinse signal is “unqualified.” An
rinse signal is “unqualified” if no detergent
signal occurred within 90 seconds prior to
the rinse signal.
“0”: Rinse manager off.
“1”: Rinse manager on.
-01 1
Rack time
rtM
10 2 It indicates the amount of time the
conveyor takes to travel one rack length.
The value is automatically updated when
the conveyor speed is changed.
sec 1 99 18
Parameter
name
Display
visualiza-
tion
Family
Nr.
Param-
eter Nr.
Parameter description Unit of
measure
Min Max Factory set-
ting[for
WT44]
Total dissolved
solid
s
tdS
11 0 This parameter displays the current total
dissolved solids.
ppm 0 9999 -
Detergent
setpoint offset
OFS
11 1
This parameter displays the conductivity
offset of the supply water.
Reset Water Conductivity Offset Reading
The Apex Controller allows you to reset the
water conductivity offset reading. To reset:
1. Fill the detergent tank with fresh water
(with no detergent or rinse agent).
2. Select “Detergent Setpoint Offset” (OFS)
parameter from “Apex Family” (APE) -->
“Test” sub-family (tSM); push one time the
“ENTER” push button: the value start to
blink. Press the “ENTER” button again: the
new offset is calculated, stored and shown.
ecounits 0 310 -
Raw
conduttivity
CrA
11 2 This parameter shows raw (not
temperature compensated) probe
conductivity readings.
ecounits 0 310 -
Compensated
conductivity
CAD
11 3 This parameter shows temperature
compensated probe conductivity readings.
ecounits 0 321 -
Wash
temperature
ttH
11 4 This parameter shows dish machine wash
temperature readings (conductivity probe
temperature sensor).
°F (or
°C)
32 212 -
Rinse Test
rtS
11 6 This parameter is used to manually turn on
the rinse aid peristaltic pump. Pump stops
automatically after 10 seconds.
“0”: No actions.
“1”: Rinse test (programmed speed).
“2”: Rinse test (max speed).
-02 0
Detergent Test
dtS
11 5 This parameter is used to manually turn on
the detergent valve. The valve stops
automatically after 10 seconds.
“0”: No actions.
“1”: Detergent test.
-01 0
ESP address
Adr
11 7 It is used to set the Ecolab Simple Protocol
ESP Network Address ID number.
- 32 127 48
Firmware
version
Fir
11 8 This parameter shows the APEX firmware
version number.
- 0 FFFF -
Check sum
CsM
11 9
It indicates the six-digit hexadecimal
checksum stored in the APEX flash memory.
--- -