A SERVICE OF

logo

Electrical data
UNIT
48SS
V-PH-HZ
VOLTAGE
RANGE
COMPRESSOR
COND
FAN
MOTOR
INDOOR
FAN
POWER SUPPLY
AWG60C
MIN WIRE
SIZE†
MAX WIRE
LENGTH
(ft)
Min Max RLA LRA FLA FLA MCA MOCP*
018 208/230-1-60 187 253 7.6 45 0.7 1.8 12.0 15 14 75
024 208/230-1-60 187 253 12.4 61 0.7 2.0 18.2 30 12 80
030
208/230-1-60 187 253 14.4 82 1.4 2.0 21.8 30 10 100
208/230-3-60 187 253 9.4 66 1.4 2.0 15.5 25 12 80
036
208/230-1-60 187 253 18.0 96 1.4 2.8 26.7 40 10 90
208/230-3-60 187 253 11.7 75 1.4 2.8 18.8 30 12 65
460-3-60 414 506 5.6 40 0.8 1.4 9.2 10 14 100
042
208/230-1-60 187 253 20.4 104 1.4 4.0 30.9 50 8 100
208/230-3-60 187 253 14.0 91 1.4 4.0 22.9 35 10 85
460-3-60 414 506 6.4 42 0.8 2.0 10.8 15 14 100
048
208/230-1-60 187 253 26.4 129 2.1 5.0 40.1 60 6 100
208/230-3-60 187 253 15.0 99 2.1 5.0 25.9 40 10 75
460-3-60 414 506 8.2 50 1.1 2.3 13.7 20 14 100
060
208/230-1-60 187 253 32.1 169 2.1 6.8 49.0 60 6 100
208/230-3-60 187 253 19.3 123 2.1 6.8 33.0 50 8 90
460-3-60 414 506 10.0 62 1.1 3.2 16.8 25 12 100
LEGEND
AWG American Wire Gage
CSA CanadianStandards Association
FLA Full Load Amps
HACR Heating, Air Conditioning and
Refrigeration
LRA Locked Rotor Amps
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
(fuses or HACR-type circuit breaker)
NEC National Electrical Code
RLA Rated Load Amps
*Fuse or HACR breaker.
†Minimum wire size is based on 60 C copper wire. If other than 60 C if
used, determine size from NEC. Voltage drop of wire must be less than
2% of rated voltage.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR breaker.
The CSA units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent-
age of voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
24