MOUNTING
2
SECURE HOSE
3A 3B
OTHER PLUMBING OPTIONS
M28709
M28675
Minimum 6 in.
Minimum 2 in.
Minimum upward
pitch of 2 in. per ft.
Hose clamps at
every connection.
Nozzle at
upward pitch.
Always consult and follow local
plumbing codes for drain pipe
size and maximum temperature
requirement.
Water in elbow.
Provide a 212°F rated Tee at the
lowest point. Do not use plastic Tee.
M28708
24V
24V
HUM
HUM
C
GT
R
RT
GF
EXT
RED
TrueSTEAM
TERMINAL
BLACK
GREEN
ORANGE
DIP 4 DIP 5
Cut a slit in the insulation half way
around the hose.
If hose slopes downhill…
Downward slope can not be more than
3 ft below humidifier steam outlet.
Clearance hole for hose and insulation.
On straight runs, use
perforated angle iron.
Otherwise, support
hose every 12 in. using
provided hooks.
Avoid sharp kinks and
prevent bends.
Clamp
Minimum upward
pitch of 2 in. per ft.
Remote Adapter Nozzle:
Always pitch upward.
If humidifier is in finished space, always install a drip pan
with wet switch. Honeywell recommends Diversitech WS-1
(wiring shown here).
Diversitech WS-1 wet
switch wiring
24 in. open air downstream.
3 in. minimum clearance from nozzle
outlet to duct.
Option 1: Plumbing to drain with
condensate pump.
Choose the plumbing option that suits your installation. Use A, B, C, or D based on type of pipe or condensate pump. Consult and follow local plumbing codes in addition to these instructions.
• Use Hartell A3X-115 condensate pump or equivalent
(212°F temperature rating, > 1 GPM pump flow rate).
• Pump must be powered when TrueSTEAM is operating.
• Use a pump with a built-in overflow sensor or install the pump
in a drip pan with wet switch wired to turn off TrueSTEAM.
• Support rubber hose every 6 in.
• PVC must be schedule 40 or higher rating.
• All plastic pipe joints are welded.
• Drain into a P-trap that will remain wetted at all times.
Draining water may be hot.
Direct and secure the hose outlet into the floor drain
to reduce risk of hot water pooling or splashing.
PLUMBING TO FLOOR DRAIN
Ideal for Installation
1-3/4 in. hole
On straight runs, use perforated angle
iron. Otherwise, secure hose every 12 in.
using provided hooks.
Seal off unconditioned space with
grommet (not provided) or caulk.
Clamp
Clamp
6 in. of straight
vertical rise.
Always install nozzle so the
outlet is pointed up.
Do not route the steam
hose through the hole in the
mounting plate.
1-1/2 IN. MINIMUM TRAP
(OR SIZE PER LOCAL CODE)
VENTED PER
LOCAL CODE
ALL PLASTIC PIPE
JOINTS ARE WELDED
M28679
3/4 IN. MNPT X SWEAT
3/4 IN. FNPT X 1-1/2 IN. PVC
1-1/2 IN. PVC
1-1/2 IN. (MINIMUM) PVC PIPE
3/4 IN. FNPT X 1-1/2 IN. PVC
3/4 IN. MNPT X 3/4 IN. CPVC
3/4 IN. FNPT X 1-1/2 IN. PVC
HOSE CLAMP
3/8 IN. BARB X 3/4 IN. MNPT
SIZE TO FIT PUMP OUTPUT
Option 2: Plumbing to a dedicated trap.
Do not cut into the
rubber steam hose.
Insert the hose clamp into
the slit and hook it onto the
rubber hose.
Nozzle at upward pitch.
12 in.
Clamps
HOSE CLAMPS AT
ALL CONNECTIONS
3/8-IN. TUBING
RATED AT 212°F
M28713
3/4 IN. FNPT X 3/4 IN. CPVC
3/4 IN. CPVC PIPE
TO PUMP
ALTERNATIVE
HOSE FROM
TrueSTEAM
Consult and follow plumbing codes for drain pipe
size and maximum temperature requirement.
Install drain hose with
continuous downhill slope.
FOR ALL OPTIONS SHOWN:
Use provided anchors
if mounting to drywall
or plaster.
COMPLETING
TRUESTEAM INSTALLATION
Refer to TrueSTEAM Installation Guide
(# 69-2285) to complete wiring and checkout.
3/4 IN. MNPT X SWEAT
3/4 IN. FNPT X 1-1/2 IN. PVC
1-1/2 IN. PVC
1-1/2 IN. (MINIMUM)
PVC PIPE
3/4 IN. FNPT X 1-1/2 IN. PVC
3/4 IN. MNPT X 3/4 IN. CPVC
3/4 IN. FNPT X 1-1/2 IN. PVC
HOSE CLAMP
3/8 IN. BARB X 3/4 IN. MNPT
M28680
ALL CONNECTIONS FROM
SOLENOID VALVE TO
DRAIN TRAP ARE SEALED
SINK
1-1/2 IN.
PVC TEE
1-1/2 IN. PVC
1-1/2 IN.
PVC
COUPLING
WELD
WELD
STAINLESS STEEL
SLOTTED BAND
COUPLING SIZED TO
FIT PIPE (COPPER,
PVC, CPVC)
SIZE TO FIT PUMP OUTPUT
ALTERNATIVE
THIS CONFIGURATION ALLOWS FOR
REMOVAL OF THE TRAP
THREADS
WELD
Option 4: Plumbing to sink trap.
3/4 IN. MNPT X SWEAT
3/4 IN. FNPT X 1-1/2 IN. PVC
1-1/2 IN. PVC
1-1/2 IN. (MINIMUM)
PVC PIPE
3/4 IN. FNPT X 1-1/2 IN. PVC
3/4 IN. MNPT X 3/4 IN. CPVC
3/4 IN. FNPT X 1-1/2 IN. PVC
HOSE CLAMP
3/8 IN. BARB X 3/4 IN. MNPT
M28681
ALL PLASTIC PIPE UNDER
SINK 1-1/2 IN. MINIMUM PVC
ALL CONNECTIONS FROM
SOLENOID VALVE TO
DRAIN TRAP ARE SEALED
SINK
COUPLING
WELD
WELD
THREADS
THREADS
WELD
WELD
WYE
1-1/2 IN. PVC
STAINLESS STEEL
SLOTTED BAND
COUPLING SIZED TO
FIT PIPE (COPPER,
PVC, CPVC)
ALTERNATIVE
THIS CONFIGURATION ALLOWS FOR
REMOVAL OF THE TRAP
SIZE TO FIT PUMP OUTPUT
Option 3: Plumbing to sink with a
dedicated trap.
3/4 IN. COPPER PIPE
3/4 IN. FNPT X SWEAT
HOSE
CLAMPS
HOSE FROM
TrueSTEAM
212°F RATED PUMP
1/2 IN. BARB X 3/4 IN. MNPT
FLEXIBLE
HOSE
M28678
SEAL ALL CONNECTIONS FROM
SOLENOID VALVE TO DRAIN STACK
3/4 IN. FNPT X
1-1/2 IN. PVC
1-1/2 IN. (MINIMUM) PVC PIPE
3/4 IN. FNPT X 3/4 IN. CPVC
3/4 IN. CPVC PIPE
3/8-IN. TUBING
RATED AT 212°F
Connect to TrueSTEAM.
Common to all plumbing options.