Agilent Technologies 665xA Video Gaming Accessories User Manual


 
Front Panel Operation 89
Programming Overcurrent Protection
When enabled, overcurrent protection removes the power supply output whenever it goes into CC operation. This prevents
the supply from indefinitely supplying the full programmed current to the load.
Setting The OCP Protection
To activate overcurrent protection, press
. The OCP annunciator will light and power supply will continue to operate
normally until it is forced into CC operation. If that occurs, the OCP circuit will trip and the power supply will remove its
output.
Checking OCP Operation
The easiest way to check this operation at any specified current is to increase the load current beyond the programmed
current value and, if necessary, decrease the programmed voltage. This will force the power supply into the CC mode (see
Figure 5-2). When OCP trips, the Prot annunciator will light and the power supply output will drop to zero.
There is now no power supply output due to an overcurrent condition. To verify this, press
and observe that the
display indicates OC.
Clearing The OCP Condition
With the OCP tripped, return to the meter mode and try to clear the condition by pressing
. Nothing will appear to
happen because the reason for the condition has not been removed. Thus, as soon as the circuit is cleared, it trips again. You
can clear the OC condition by:
Increasing the load resistance to lower the output current below the programmed current value, or
By raising the programmed current to a value above that required by the load.
Clear the fault by either of the above methods. Then clear the OCP circuit by pressing
. The Prot annunciator will
go off and the power supply output will be restored to normal.
If desired, you can also restore the output by disabling the OCP function (press
to turn off the OCP annunciator).
This restores the output but does not clear any condition that may have caused OCP to trip.
Note Under certain conditions, the OCP circuit may fail to clear because load demand occurs before the power
supply has time to build up the required output current capacity. In such cases, disable the output (press
before clearing the OCP circuit). After OCP is cleared, enable the power supply output.
CV Mode VS. CC Mode
Once you program a voltage (V
S
) and a current (I
S
) in Figure 5-2, the power supply will try to maintain itself in either CV or
CC mode, depending on the impedance of the load (R
L
). If the load demands less current than I
s
, operation will be in CV
mode with the voltage maintained at V
s
. The output current will be at some value below I
s
as determined by V
S
÷ R
L
.
If the current increases beyond I
S
(see R
L2
), the supply will switch to CC mode by varying its output voltage to maintain a
constant current value of I
s
. As more current is demanded, the voltage decreases to maintain the increased current level. If
the load current increases to the maximum output of the power supply, the output voltage will be maintained at a near-zero
level.