13
An
a
l
ogu
e
S
i
gn
a
l
Pro
c
e
ss
i
ng
FP0 Analogue Units
■ Multimode A/D, D/A conversion ■ High resolution: 12-bit
Voltage, current and temperature selectable
■ 2 analogue inputs (FP0-A21): ■ High conversion speed
-10 to + 10V, 0 to 5V, 0 to 20mA, FP0-A04V, FP0-A04I: 500µs
8 analogue inputs (FP0-A80):
-10 to + 10V, 0 to 5V, -100 to + 100mV, 0 to 20mA
■ PID instruction with auto tuning
■ 1 analogue output (FP0-A21): -10 to + 10V, 0 to 20mA
4 analogue outputs (FP0-A04V): -10 to + 10V
■ Screw terminal connection
4 analogue outputs (FP0-A04I): 4 to 20mA
Fea
t
ur
e
s
The analogue units can be used with the FP0 and FP∑ (Sigma) so wide range applications are possible from small-
scale machines to factory production systems.
Each CPU supports up to 3 FP0 analogue units. Combination with digital and analogue expansion units is freely allowed.
Highest performance is offered with 12-bit resolution. With a current and voltage output conversion time of up to
500µs, the units are capable of high-speed processing.
The multimode FP0 analogue unit can be configured via the DIP switches on the front side into the required analogue ranges.
Communication with the FP0 CPU unit is achieved via the expansion bus. The expansion bus is automatically connected after
the FP0 analogue unit is connected to the FP0 CPU unit.
Note: Function blocks for the FPWIN Pro programming system can be downloaded free of charge from our Web site.
FP0-A04V
4 Outputs
FP0-A04I
4 Outputs
FP0-A21
2 Inputs/1 Output
FP0-A80
8 Inputs
07/2007