Omega CN1166 Video Game Controller User Manual


 
Some of the parameters which do not apply to a particular instrument
configuration (e.g. PB2 on a single output instrument) will accept reads & writes.
Others will accept reads only, and will return an exception if an attempt is made
to write values to them. The values read will in all cases be undefined. It is the
user’s responsibility to make sure that values read reflect a possible state of the
instrument.
4-10 Volume II O077-4
No. Parameter Notes
Segment Parameters - Program 3
1300 Run Program (value = Delayed Start value) Write only
1301 No. of Cycles Programmed 1 to 9999 plus 10000 (INF)
1302 Timebase 0 = hours/mnutes, 1 = minutes/seconds
1303 Guaranteed Soak Band value 0 (OFF), 1 to span
1304
to
1319
Final Setpoint values
(Soak = -32768, End = -16384)
Segment 1 at address 1304
ß
Segment 16 at address 1319
1320
to
1335
Rate values (Soak = -32768, End =
-16384)
Segment 1 at address 1320
ß
Segment 16 at address 1335
1336
to
1351
Time values Segment 1 at address 1336
ß
Segment 16 at address 1351
1352 Event Marker settings
Bit 0 = Event 16 Þ Bit 15 = Event 1
Segment Parameters - Program 4
1400 Run Program (value = Delayed Start value) Write only
1401 No. of Cycles Programmed 1 to 9999 plus 10000 (INF)
1402 Timebase 0 = hours/minutes, 1 =
minutes/seconds
1403 Guaranteed Soak Band value 0 (OFF), 1 to span
1404
to
1419
Final Setpoint values
(Soak = -32768, End = -16384)
Segment 1 at address 1404
ß
Segment 16 at address 1419
1420
to
1435
Rate values (Soak = -32768, End =
-16384)
Segment 1 at address 1420
ß
Segment 16 at address 1435
1436
to
1451
Time values Segment 1 at address 1436
ß
Segment 16 at address 1451