O077-4 Volume II 4-9
No. Parameter Notes
34 Profiler Commands Write only - see Subsection 4.6.
35 Power Fail Recovery 0 = Cold start, 1 = Warm start
36 Guaranteed Soak Type 0 = disabled, 1 = enabled, 2 = manual
37 Cycles Remaining Read only
Instrument ID Parameters
121 Manufacturer ID Read only - 231
122 Equipment ID Read only - 6400
Segment Parameters - Program 1
1100 Run Program (value = Delayed Start value) Write only
1101 No. of Cycles Programmed 1 to 9999 plus 10000 (INF)
1102 Timebase 0 = hours/minutes, 1 =
minutes/seconds
1103 Guaranteed Soak Band value 0 (OFF), 1 to span
1104
to
1119
Final Setpoint values
(Soak = -32768, End = -16384)
Segment 1 at address 1104
ß
Segment 16 at address 1119
1120
to
1135
Rate values (Soak = -32768, End =
-16384)
Segment 1 at address 1120
ß
Segment 16 at address 1135
1136
to
1151
Time values Segment 1 at address 1136
ß
Segment 16 at address 1151
1152 Event Marker settings
Bit 0 = Event 16 Þ Bit 15 = Event 1
Segment Parameters - Program 2
1200 Run Program (value = Delayed Start value) Write only
1201 No. of Cycles Programmed 1 to 9999 plus 10000 (INF)
1202 Timebase 0 = hours/minutes, 1 =
minutes/seconds
1203 Guaranteed Soak Band value 0 (OFF), 1 to span
1204
to
1219
Final Setpoint values
(Soak = -32768, End = -16384)
Segment 1 at address 1204
ß
Segment 16 at address 1219
1220
to
1235
Rate values (Soak = -32768, End =
-16384)
Segment 1 at address 1220
ß
Segment 16 at address 1235
1236
to
1251
Time values Segment 1 at address 1236
ß
Segment 16 at address 1251
1252 Event Marker settings
Bit 0 = Event 16 Þ Bit 15 = Event 1